Emergency Contacts Emergency Access List Tenant Emergency Action Plan Fire and Life Safety Systems Fire Prevention Tenant Safety Wardens Fire Response Evacuation Procedures Lockdown Procedure Tenant Responsibilities Fire Drills Inclement Weather Hurricane Season Bomb Threat Civil Disturbance Elevator Emergency Suspicious Persons / Active Shooter Terrorism Medical Emergency Power Failure Hazardous Materials Spills or Releases
Fire and Life Safety Systems
Page: 4 of 4 Back  | 

ALARM TYPE
RESPONSE
  • Smoke in any elevator lobby
  • Voice EVAC sounds
  • Strobes flash on alarm floor, floor above, floor below, and bridge level lobby
  • Stair pressurization fans are activated and HVAC on alarm floor is shut off
  • If smoke is detected on bridge level (2nd floor) low rise elevator lobby, low rise elevators are directed to the 4th floor. If it detected on the bridge level high rise elevator lobby, all high rise elevators are directed to the 15th floor.
  • If smoke is detected in any elevator lobby (excludes bridge level), elevators are called to the bridge level (2nd floor).
  • Smoke in duct work
  • Voice EVAC sounds
  • Strobes flash on alarm floor, floor above, floor below, and bridge level lobby
  • Stair pressurization fans are activated and HVAC on alarm floor is shut off
  • Elevators continue to operate
  • Pull stations
  • Voice EVAC sounds
  • Strobes flash on alarm floor, floor above, and the floor below.
  • Stair pressurization fans are activated and HVAC on alarm floor is shut off
  • Elevators continue to operate

 